Data Centers - Shanghai Facility
In 2007, following comprehensive research, DataPipe signed a long term lease for data center space in Shanghai. The facility we selected has the highest standards for reliability, security and redundancy in Shanghai. Strategically located in Pudong, this purpose built data center features a state-of-the-art network, power and environmental infrastructure. DataPipe staffs this center with our own specially trained and highly experienced system engineering staff who actively manage and maintain our systems 24 hours a day, 7 days a week, 365 days a year.
Custom Design
- Data center layout and security system based on ISO27001/BS7799 environmental safety standard
- ISO 9001 and SunToneTM Certified
- FM 200 Fire Suppression System
- Double Interlock Pre-action Sprinkler System
- Carrier neutral facility with fiber from major providers delivered via 2 separate Points of Entry located on opposite sides of the facility
- DataPipe network featuring redundant fiber sources and redundant aggregate switches and core routers
- DataPipe network featuring direct BGP peering with China Telecom and China Netcom
- Dual Riser Configuration - Both power and data are delivered to each rack via two separate Risers from opposite sides of the building
- Satellite access available
Security
- 24/7 on-site building and network monitoring
- 24/7 security staff, strictly enforced security procedures
- Card access control system and photo ID badging
- Bio-metric and Proximity authentication for critical areas
- Access control, intrusion zone control, elevator control, CCTV alarm interface
- Visitors are escorted by authorized personnel at all times
- 24 hour internal and external video surveillance, 60 day retention policy
- Multiple mantraps with reinforced walls
Power Conditioning
- 6400 KVA from 2 separate sub-stations
- 500KVA UPS modules with N+1 configuration with 30 minutes battery backup time
- Dual power supply risers
- Four 1000KVA generator sets (24-hour continuous full supply)
HVAC Temperature Controlled Environment
- Indoor temperature at 20°C +/- 2°C
- Relative humidity range from 50% +/-10%
- Chilled Water Type CRAC unit
- Chiller plant is in N+1 with RING configuration , redundant tower water supply
- Water piping outside core area, floor curb zoning to CRAC controls water leakage
- Raised floor to provide uniform cooling distribution